Phone: +1 758-453-0049
E-mail: info@slbs.org
Bisee, Saint Lucia LC04301

ISO 10295-2:2009

Fire tests for building elements and components — Fire testing of service installations — Part 2: Linear joint (gap) seals

Jan 19, 2009

General information

90.93     Oct 26, 2020

ISO

ISO/TC 92/SC 2

International Standard

13.220.50     91.140.01  

English  

Buying

Published

Language in which you want to receive the document.

Scope

ISO 10295-2:2009 specifies the heating conditions, methods of test and criteria for the evaluation of the ability of a linear joint seal to maintain the fire integrity and thermal insulation of a fire-separating element at the joint being sealed. The purpose of the tests is to assess the integrity and insulation performance of the linear joint seals, including the effects of induced movement in those cases where the joint is designed to accommodate movement and has a width greater than 20 mm.
It is not the intention of this part of ISO 10295-2:2009 to provide quantitative information on the rate of leakage of smoke and/or gases, or on the transmission or generation of fumes, although such phenomena can be recorded in describing the general behaviour of specimens during the test. It is not the intention of this part of ISO 10295-2:2009 to evaluate joint seals where special test procedures already exist, e.g. doors, partitions, penetrations, pipes, ducts and cables.

Life cycle

NOW

PUBLISHED
ISO 10295-2:2009
90.93 Standard confirmed
Oct 26, 2020

CORRIGENDA / AMENDMENTS

Corrected by
ISO 10295-2:2009/Cor 1:2009

REVISED BY

ABANDON
ISO/PWI 10295-2

Preview

Only informative sections of projects are publicly available. To view the full content, you will need to members of the committee. If you are a member, please log in to your account by clicking on the "Log in" button.

Login